Ω
CableSize

NEC-reference grade

Wire & Cable
Size Calculator

Instantly size conductors for DC, single-phase, and three-phase AC circuits. Computes the minimum AWG by both ampacity and voltage drop, picks the governing constraint, and flags when no listed conductor meets your target.

AWG 14 – 4/0Copper & Aluminum60 / 75 / 90 °C ratingsDC · 1φ · 3φ ACNEC 310 ampacity

Calculator

fill in circuit parameters → instant result

Circuit Parameters

Load
Enter circuit parameters above and press Calculate

AWG Reference Table

NEC 310.12 — ≤3 conductors, 30 °C ambient
Size (AWG)Area (kcmil)Resistance (Ω/kft)Copper Ampacity (A)Aluminum Ampacity (A)
CuAl60 °C75 °C90 °C60 °C75 °C90 °C
144.113.07005.0600151525
126.531.93003.1800202530152025
1010.381.21002.0000303540253035
816.510.76401.2600405055304045
626.240.49100.8080556575405055
441.740.30800.5080708595556575
352.620.24500.403085100110657585
266.360.19400.3190951151307590100
183.690.15400.253011013014585100115
1/0105.600.12200.2010125150170100120135
2/0133.100.09670.1590145175195115135150
3/0167.800.07660.1260165200225130155175
4/0211.600.06080.1000195230260150180205